Fireye UV1A6 Flame Scanner is used with the M-Series, M-Series II, and MicroM controls as well as the FLAME-MONITOR, BurnerLogix and Nexus System. The UV1A6 scanner comes with a 6 ft. cable rated for Tray Cable – Exposed Run (TC-ER) and complies with the crush and impact requirements of the standard for metal-clad cable, UL 1569.
The UV tube is made of quartz and is filled with a gas that ionizes when struck by UV radiation from the flame. In the absence of UV radiation, the gas acts as an insulator between two electrodes that are mounted inside the tube. These electrodes are energized continuously by a high voltage. During combustion, UV radiation ionizes the gas, causing current pulses to flow between the electrodes. These current pulses result in a flame signal which is transmitted to the amplifier in the control, where it is processed to energize or hold in the flame relay.
Fireye UV1A6 flame scanner is recommended for detecting flames from standard fuel gases, some waste gases and light oil fuels such as No. 2 oil. Flames from heavier oils can be detected with UV scanners but the unburned fuel shroud and/or atomization shroud can block the passage of the UV from the flame zone to the UV tube, causing nuisance burner/boiler trips. Infrared detection is recommended for fuel oil heavier than No. 2, and some installations where waste gases are burned together with natural gas as the main flame.
David Marks –
UV1A series flame scanner is the go-to product for flame detection. Very high sensitivity.
Harry T –
Nice product