The Honeywell RM7890A1015 is a Microprocessor-based integrated burner control (120V) designed for single burner applications using gas, oil, coal, or combination fuel. It surpasses conventional controls in providing safety, functional capability, and advanced features.
Functions encompass automatic burner sequencing, flame supervision, system diagnostics, and troubleshooting with external voltage checks. It offers application flexibility and communication interface capability.
Equipped with five LEDs for sequence data, a five-function Run/Test switch, and interchangeable plug-in flame amplifiers, it allows optional local or remote annunciation of RM7840 operation and faults. Nonvolatile memory preserves history and lockout status after a power loss, compatible with existing Honeywell flame detectors. Additionally, it includes a dust cover and an AirFlow switch check option.
- Flame Establishing Period – Pilot, 4 sec or 10 sec
- Flame Establishing Period – Main, 10 sec or 15 sec
- Early Spark Termination – Yes, 5 sec
- Required Components: Q7800A,B Universal Wiring Subbases, R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier
- ST7800A Plug-in Purge Timer Card
Reviews
There are no reviews yet.