The Honeywell RM7895A2014 is a Microprocessor-based Integrated On-Off Primary Burner Control (120V, 50/60Hz) featuring Shutter Drive Output, Valve Proving, and LED Fault Annunciation. Offering safety and advanced capabilities beyond typical controls, it requires RM/EC7800 2000 Series with subbases Q7800A2005/U, Q7800B2003/U, Q7800B2011/U.
Functions encompass automatic burner sequencing, flame supervision, system diagnostics, and external voltage checks. Enjoy flexibility with 5 LEDs for sequence data, a 5-function Run/Test switch, interchangeable plug-in flame amplifiers, and optional local or remote annunciation of RM7840 operation and faults.
Nonvolatile memory preserves history and lockout status after power loss, compatible with existing Honeywell flame detectors. The unit also includes a dust cover and AirFlow switch check option.
- Flame Establishing Period – Pilot, 4 sec or 10 sec
- Flame Establishing Period – Main, 10 sec or 15 sec
- Early Spark Termination – Yes, 5 sec
- Required Components: Q7800A,B Universal Wiring Subbases, R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal
- Amplifier, ST7800A Plug-in Purge Timer Card